母(mu)線(xian)槽系統(tong)(tong)是一(yi)個高(gao)(gao)效(xiao)輸(shu)(shu)送電(dian)(dian)(dian)流(liu)的配電(dian)(dian)(dian)裝置,尤其(qi)適應(ying)了(le)越(yue)來越(yue)高(gao)(gao)的建(jian)筑(zhu)物(wu)和(he)大規模工(gong)廠經(jing)濟合理(li)配線(xian)的需要(yao)。隨著現(xian)(xian)代(dai)化工(gong)程設施(shi)和(he)裝備的涌(yong)現(xian)(xian),各行各業(ye)的用電(dian)(dian)(dian)量(liang)迅(xun)增,尤其(qi)是眾多的高(gao)(gao)層建(jian)筑(zhu)和(he)大型(xing)廠房車間的出現(xian)(xian),作(zuo)為輸(shu)(shu)電(dian)(dian)(dian)導線(xian)的傳(chuan)統(tong)(tong)電(dian)(dian)(dian)纜現(xian)(xian)在大電(dian)(dian)(dian)流(liu)輸(shu)(shu)送系統(tong)(tong)中(zhong)(zhong)已(yi)不能(neng)滿足要(yao)求(qiu),多路電(dian)(dian)(dian)纜的并聯使(shi)(shi)用給現(xian)(xian)場安裝施(shi)工(gong)連接(jie)(jie)帶(dai)來了(le)諸多不便。作(zuo)為一(yi)種新(xin)型(xing)配電(dian)(dian)(dian)導線(xian)應(ying)運(yun)而生,與傳(chuan)統(tong)(tong)的電(dian)(dian)(dian)纜相比,在大電(dian)(dian)(dian)流(liu)輸(shu)(shu)送時充分體(ti)現(xian)(xian)出它的優越(yue)性,同時由(you)于采(cai)用了(le)新(xin)技術、新(xin)工(gong)藝,大大降低的母(mu)線(xian)槽兩端(duan)部連接(jie)(jie)處及(ji)分線(xian)口插接(jie)(jie)處的接(jie)(jie)觸(chu)電(dian)(dian)(dian)阻和(he)溫升,并在母(mu)線(xian)槽中(zhong)(zhong)使(shi)(shi)用了(le)高(gao)(gao)質量(liang)的絕緣材料,從(cong)而提高(gao)(gao)了(le)母(mu)線(xian)槽的安全可靠性,使(shi)(shi)整個系統(tong)(tong)更加完(wan)善(shan)。
一、工作環境條件(1)環境溫度:-5°C至+50°C;
(2)相對濕(shi)(shi)度(du):日平均值不(bu)超(chao)過(guo)95%,月(yue)平均值不(bu)超(chao)過(guo)90 %(25°C),相對濕(shi)(shi)度(du)應符合GB7251.1-1997及GB7251.2-1997標準;
(3)海拔高度(du):小于1000米;
(4)額定工作電壓:交流600V及以(yi)下(xia);
(5)額定頻(pin)率:50Hz;
(6)額定電流(liu):630A~5000A。
二(er)、技術要求全封閉(bi)式(shi)配電(dian)母線槽應設(she)計(ji)合理(li),品質(zhi)及性能(neng)必須優(you)質(zhi)、穩定和可靠(kao)。具有阻抗(kang)低(di)、散熱好、電(dian)壓降低(di)、阻燃、防(fang)火阻隔、防(fang)濺(jian)水(shui)、耐機械沖(chong)擊(ji)、防(fang)爆的性能(neng),并應有國(guo)內或國(guo)外成功運行的實例證明。
1.母線(xian)槽主要材質的(de)要求
①導(dao)體為高導(dao)電率的(de)銅(tong)板,銅(tong)的(de)純度必須(xu)>99.9%,銅(tong)板表面要求全長鍍(du)銀或鍍(du)錫。
②絕(jue)(jue)緣材料應達到B級(ji)及以上的絕(jue)(jue)緣等級(ji),能耐受130°及以上高溫(wen),保證在高溫(wen)場合的長絕(jue)(jue)緣壽命與可靠性。
③裝甲型(xing)母線槽的(de)防(fang)護等級(ji)為IP54及以上。
④應采用100%容量的PE排;
⑤外殼(ke)側面應(ying)采用(yong)優質(zhi)鍍鋅無縫鋼板或(huo)優質(zhi)鋁合(he)金(jin),加強(qiang)抗外力沖擊能力,并具有低的磁滯渦(wo)流損耗(hao)特性。
⑥母(mu)線槽外殼應完全密封以(yi)免機(ji)械(xie)損傷和灰(hui)塵進入。
⑦外殼需(xu)經過良好的防腐(fu)蝕處理。
⑧電(dian)磁兼容性(xing)應(ying)符合EN50081的(de)要求。
2.母線(xian)槽結構(gou)的(de)要求(qiu)
①母線(xian)槽采用密集型“三明治結構”。
②除插接口處,其它部分母(mu)線排之間(jian)沒有縫隙。
③母線槽內的連(lian)續空間應采(cai)用隔板封(feng)閉,防止火災(zai)發生(sheng)時濃煙(yan)(yan)及(ji)氣(qi)體通過母線槽散播。母線槽穿墻和地板時,不(bu)會形成(cheng)“煙(yan)(yan)囪(cong)效應”的燃燒途徑。母線槽絕(jue)緣材料應通過阻燃測試。
④母線槽的(de)連接性能應可(ke)靠,保(bao)證具有盡量小的(de)接觸電阻;母線槽的(de)連接操作(zuo)應當滿足快速連接的(de)要求,應使(shi)用單螺栓進行連接,并(bing)且應有力矩控制措施。
⑤全封(feng)閉式母線(xian)(xian)槽應(ying)具(ju)有優良的(de)封(feng)閉性能(neng),能(neng)夠耐(nai)受較惡(e)劣的(de)環境污染。在產品壽命期內(nei),母線(xian)(xian)槽內(nei)部(bu)應(ying)當保持清潔,無灰塵(chen)等(deng)積聚物,母線(xian)(xian)槽外部(bu)嚴禁使用遮雨(yu)棚(peng)等(deng)類似(si)雨(yu)傘的(de)附件來增加(jia)母線(xian)(xian)槽的(de)防護等(deng)級。
⑥連接(jie)(jie)頭:母線(xian)(xian)連接(jie)(jie)頭應(ying)采(cai)(cai)用現有國(guo)內外(wai)先(xian)進技術,確保導體(ti)可(ke)(ke)(ke)靠連接(jie)(jie),安(an)裝準確、快速(su)、方便(bian)。母線(xian)(xian)連接(jie)(jie)頭應(ying)具有獨立和(he)可(ke)(ke)(ke)拆(chai)卸(xie)特(te)性,且規格相同的連接(jie)(jie)頭可(ke)(ke)(ke)以互換,便(bian)于安(an)裝及維護。連接(jie)(jie)頭應(ying)考慮運行(xing)狀態下母線(xian)(xian)槽(cao)熱脹冷縮對設(she)備的影(ying)響,且接(jie)(jie)頭的設(she)計(ji)不會降低母線(xian)(xian)的性能。連接(jie)(jie)頭要求采(cai)(cai)用力矩(ju)(ju)控制螺栓,無需(xu)特(te)殊力矩(ju)(ju)扳(ban)手(shou)或人工掌握力矩(ju)(ju)大(da)小(xiao)。
3.產品的性能要求
①整體接地(di)系統,杜絕可能(neng)情況下人身傷害事故發(fa)生的可能(neng)。
②母線(xian)(xian)槽滿足TN-S供電(dian)要求,5組(zu)銅(tong)排(相線(xian)(xian)3組(zu),N線(xian)(xian)和PE線(xian)(xian)各1組(zu))。母線(xian)(xian)槽應選(xuan)擇(ze)具有100%額定容(rong)量(liang)的(de)(de)PE銅(tong)排作為接地(di)(di)導體,為接地(di)(di)故障提供可靠的(de)(de)接地(di)(di)路徑,保(bao)證足夠(gou)的(de)(de)安全性。當發生高容(rong)量(liang)的(de)(de)接地(di)(di)故障時,可有效接地(di)(di)以保(bao)護(hu)整個系統。
③高導電(dian)效率,電(dian)阻(zu)消耗小,阻(zu)抗及電(dian)壓(ya)降不(bu)得超過(guo)技術參數表所列數值(zhi)。
④高性能的短路防(fang)護,整個系統(tong)應能承受15~75kA持續時間1秒的短路電流。
⑤動穩定(ding)性和耐(nai)壓:母線槽(cao)的過短路電流能力(li)應滿足設計要求;所(suo)有母線部件,如(ru)直(zhi)線段、彎頭、法蘭等都應滿足3500V耐(nai)壓要求。
⑥溫升(sheng):母線槽內各點的(de)溫升(sheng)應當均勻,任何(he)導電體(ti)包括連(lian)接頭的(de)溫升(sheng)應當不超過70°C。
4.環境保護要求
主要絕緣材料在火災時(shi)不(bu)能放出有毒氣體(ti)。
5.母線槽與變壓器及開關柜的(de)接口
母(mu)線(xian)槽(cao)與開(kai)關柜(低(di)壓(ya)柜的饋(kui)線(xian)柜、MCC柜的進(jin)線(xian)柜)接口由母(mu)線(xian)槽(cao)廠家負責(ze)解(jie)決,廠家應根(gen)據低(di)壓(ya)柜的接口要求及現場情況,設置(zhi)盤接頭或轉(zhuan)接箱。
6.使用壽命
母線槽應(ying)為(wei)30年免維護。
7.型式試驗
產品(pin)應提供國家(jia)權威機構出具(ju)有效(xiao)的(de)型式試(shi)驗報告,產品(pin)通過的(de)型式試(shi)驗項目(mu)如(ru)下(xia):
機械負載試驗
溫升試驗
短路強度試驗
保護電路連續性試驗
額定峰值耐受(shou)電(dian)流試(shi)驗
額定短時(shi)耐受電流試驗
防護等級耐受試驗
介電強度試驗
絕緣強度試(shi)驗(yan)(yan)或沖(chong)擊電壓耐受試(shi)驗(yan)(yan)
驗證電阻、電抗
驗(yan)證電氣間隙和爬電距離
8.出廠試驗
產品出廠(chang)應經(jing)過100%的(de)高壓絕(jue)緣(yuan)試(shi)驗(yan)(yan)(DC 3500V)及(ji)國家有關(guan)標準規定(ding)的(de)試(shi)驗(yan)(yan)并提供完整的(de)出廠(chang)試(shi)驗(yan)(yan)報(bao)告,業主可到現場考(kao)察及(ji)監督產品的(de)生(sheng)產流程及(ji)檢驗(yan)(yan)過程。
9.特殊說明
1)母(mu)線(xian)槽外殼顏色由設計聯絡階段確定。
2)中標(biao)單位(wei)應提(ti)供所(suo)選用(yong)母線槽(cao)的全(quan)部規格清單交甲方。
3)母線槽、接頭(tou)、彎(wan)頭(tou)、伸縮節及其它附件、安裝(zhuang)支架應送樣品(pin)(pin)交甲(jia)方(fang)審核通(tong)過(guo),滿足(zu)甲(jia)方(fang)要求的樣品(pin)(pin)交甲(jia)方(fang)封樣留(liu)存。